VoltConvert
Home / Converters / kVA to Amps

kVA to Amps

Convert apparent power (kilovolt-amps) to current (amps) for single-phase and three-phase circuits. The formula and a worked example are shown below the calculator.

Result
Ad slot — your AdSense code goes here once approved

Formula

Single phase: I (A) = 1000 × S (kVA) ÷ V (V)

Three phase (line-to-line voltage): I (A) = 1000 × S (kVA) ÷ (√3 × VL-L)

Worked example

A 25 kVA three-phase generator at 400 V line-to-line: I = 1000 × 25 ÷ (1.732 × 400) = 36.08 A per line.

Reference table

Quick reference

kVAAmps @ 230 V (1φ)Amps @ 400 V (3φ)
14.351.44
521.747.22
1043.4814.43
25108.736.08
50217.3972.17
100434.78144.34

Where this shows up in the real world

Transformer and generator nameplates list kVA, but breakers, conductors and panel schedules are sized in amps — so this conversion sits at the start of nearly every service-sizing job. A US electrician checking whether a 75 kVA transformer can feed a 208Y/120V panel, or a UK contractor sizing the supply for a 50 kVA three-phase machine at 400V, is doing exactly this math before opening a code book.

Common mistakes to avoid

The classic error is mixing up line-to-line and line-to-neutral voltage in three-phase work: use the line-to-line figure (208V, 400V, 480V) with the √3 formula, never the phase voltage. The second trap is forgetting that the kVA rating is the transformer's ceiling, not the load — size conductors from the actual load current, and protection per NEC Article 450 or your local code.

Frequently asked questions

Why does three phase divide by √3?

In a balanced three-phase system, power is shared across three conductors. Using line-to-line voltage, the relationship S = √3 × V × I applies, so solving for current introduces √3 (about 1.732).

Is kVA the same as kW?

No. kVA is apparent power; kW is real power. They are related by the power factor: kW = kVA × PF. Generators and transformers are rated in kVA because they must carry the full apparent current.

Which voltage should I use?

For single phase, use the line-to-neutral supply voltage (e.g. 230 V in Pakistan/EU, 120 V in North America). For three phase, use line-to-line voltage (e.g. 400 V or 480 V).

Related converters

Amps to kVA  ·  kVA to kW  ·  kW to Amps

Written by the VoltConvert team. Every formula on this site follows standard SI and electrical-engineering definitions (IEC/NEC conventions), and each calculator shows its working so results can be independently verified.
Last updated: June 12, 2026